Superheat Calculator
Read the suction pressure off the gauge, measure the suction line temperature with a clamp thermometer, and get the superheat — or switch to subcooling mode for the liquid line. The R-410A, R-22, and R-134a pressure-temperature tables are built in, so no paper chart is needed.
Frequently Asked Questions
What is superheat?
The gap between the actual temperature of the vapor leaving the evaporator and the saturation temperature for the current suction pressure. Superheat = suction line temperature − saturation temperature at suction pressure. It proves the refrigerant has fully boiled to vapor before reaching the compressor.
What is subcooling?
The mirror image on the high side: saturation temperature at liquid-line pressure minus the actual liquid line temperature. It shows how far the liquid has cooled below its condensing point before the metering device, and it is the number most technicians lean on to confirm charge on a TXV system.
How do I use a PT chart?
Read the gauge pressure, find the matching saturation temperature for your refrigerant on the PT chart, then subtract: line temperature minus saturation temperature for superheat, saturation temperature minus line temperature for subcooling. This calculator does the lookup and the subtraction for you.
What is a normal superheat or subcooling?
For most residential TXV systems, target superheat is about 8–15°F and target subcooling about 8–15°F, depending on refrigerant and manufacturer. Fixed-orifice (piston) systems use a target superheat chart that varies with indoor wet-bulb and outdoor dry-bulb temperatures, so a single fixed number does not apply — check the unit data plate.
What does high or low superheat mean?
High superheat usually points to low charge, a restricted metering device, or low airflow across the evaporator. Low or zero superheat means liquid may be reaching the compressor, which can damage it — a common sign of overcharge or a metering device stuck open. Treat these as diagnostic clues, not a diagnosis on their own.
Do I need a different chart for each refrigerant?
Yes. The same pressure means a different saturation temperature for each refrigerant — 40°F saturation is 118.8 psig on R-410A, 68.6 psig on R-22, and 35.0 psig on R-134a. Reading the wrong refrigerant's chart is one of the most common bad-reading mistakes.