HVAC Duct Size Calculator
What size duct do you need for a given airflow? Enter the required CFM and this page sizes the duct with the equal-friction method: it solves for the round diameter at your friction rate, rounds up to the nearest standard size, checks the air velocity, and lists equivalent rectangular sizes. The CFM itself should come from a room-by-room Manual J load calculation or your equipment's rated airflow — not a guess.
0.10 is the standard residential design rate (ACCA Manual D baseline). A real Manual D design derives this from the blower's available static pressure divided by the total equivalent length of the longest run — it often lands nearer 0.06, which sizes ducts a step or two larger.
Method: equal-friction equation for galvanized round duct, FR = 0.109136 × CFM^1.9 ÷ D^5.02 (inches of water per 100 ft), solved for diameter; rectangular equivalents by the Huebscher formula, De = 1.30 × (W×H)^0.625 ÷ (W+H)^0.25. Velocity targets: supply 700–900 FPM, return 600–700 FPM; standard residential friction rate 0.08–0.10 in. w.g. per 100 ft — per ACCA Manual D as summarized by multiple published duct-sizing references (HVAC Duct Calculator CFM chart, Duct Sizing Calculator chart, Aircondlounge Manual D chart). Published anchors: 100 CFM → 6 in round (509 FPM, ~0.085 in. w.g.); 200 CFM → 8 in (573 FPM, ~0.075); 400 CFM → 10 in (734 FPM); 2,000 CFM at 0.10 → ~18.1 in exact diameter. Last verified November 2026.
Frequently Asked Questions
What size duct do I need for 200 CFM?
An 8-inch round duct. At the standard 0.10 in. w.g. friction rate, 200 CFM needs an exact diameter of about 7.6 inches, which rounds up to the standard 8-inch size; air moves at about 573 FPM with about 0.075 in. w.g. of friction — inside the usual limits. The rectangular equivalent is roughly 10×6 inches (equivalent round diameter about 8.4 in).
What is the equal-friction method?
Every duct run is sized to lose the same amount of pressure per foot of length — the friction rate, in inches of water column per 100 feet. The traditional residential default is 0.10, though a proper Manual D calculation often derives a lower rate (near 0.06) from the blower's available static pressure, which sizes ducts a step or two larger.
What air velocity should a residential duct run at?
Supply ducts: 600–900 FPM (branches 600–700 FPM, main trunks 700–900 FPM). Return ducts: 500–700 FPM. Above 900 FPM on a supply run (or 700 FPM on a return) you start hearing rushing air at the registers. Below the range, distant rooms get poor air distribution.
How do I convert a round duct to a rectangular one?
Use the Huebscher equivalent-diameter formula: De = 1.30 × (width × height)^0.625 ÷ (width + height)^0.25. Two ducts with the same equivalent diameter have the same friction behaviour. Note that equal friction is not equal area — a very flat rectangle has more surface and more friction than a square one of the same area.
Does flexible duct size the same as rigid duct?
No. Flex duct carries roughly 15–20% less airflow than rigid metal duct at the same diameter, and installed flex with sag performs worse than fully stretched flex. Size flex duct one step larger than the rigid size this calculator gives, and keep flex runs short and straight.
Where does the CFM number come from?
From a Manual J load calculation (room-by-room heat loss and gain) or from your equipment's rated airflow — about 400 CFM per ton of cooling is a common rule of thumb. Do not guess CFM from floor area alone; an undersized duct starves the room, an oversized one wastes money and can be noisy.